Filter by Category
23 of 23 sections
Insulation R-Values by Climate Zone
Zone 5A: Ceiling R-49, Wall R-20 or R-13+5ci, Floor R-30
Minimum insulation requirements for climate zone 5A (Boston, MA area). Ceiling assembly minimum R-49 value. Wall assemblies must achieve R-20 (cavity + continuous) or R-13 cavity with R-5 continuous insulation. Floor assemblies over unconditioned space require R-30 minimum.
Air Barrier & Insulation Installation
Requires continuous air barrier, tested ≤ 3 ACH50 for new construction
New construction must maintain continuous air barrier at thermal envelope. Blower door testing required to verify air tightness of ≤ 3 ACH50 (air changes per hour at 50 Pa). All penetrations, rim joists, and transitions must be sealed.
Fenestration U-Factor
Zone 5A: U-0.30 max
Window and sliding glass door assemblies in Zone 5A must not exceed U-factor of 0.30 (whole window, including frame). Fixed skylights U-0.38 max. Frameless glass skylights follow different requirements.
Vapor Retarders
Class I or II required on warm side in Zone 5A
Climate Zone 5A requires vapor retarder (≤ 1 perm) on the warm side of wall assemblies. Class I (≤ 0.1 perm) includes polyethylene sheet, foil-faced insulation. Class II (0.1–1 perm) includes kraft paper facings. Proper placement critical for moisture management.
Basement Wall Insulation
R-15ci or R-19 cavity
Basement walls below-grade must be insulated to R-15 continuous insulation OR R-19 cavity insulation. Continuous insulation (ci) preferred for thermal bridging reduction. Insulation may be placed on interior or exterior of wall; interior placement must be protected with fire-rated covering.
Duct Sizing & Installation
Return air must equal supply, max 0.05" static per 100ft
Supply and return ductwork must be sized so total return air flow equals total supply air flow. Ductwork friction loss limited to 0.05 inches of water column per 100 feet of duct. Ducts must be sealed with mastic or tape rated for applications.
Dryer Exhaust
Max 35ft equivalent, 4" smooth metal duct
Clothes dryer exhaust must use 4-inch smooth metal ductwork (rigid or flexible). Maximum equivalent length 35 feet (includes fittings and elbows; each elbow counts as 5 feet equivalent). Duct must terminate outside with damper. Flexible duct not to exceed 8 feet or 2 elbows.
Bath Fan Requirements
50 CFM intermittent or 20 CFM continuous
Bathroom ventilation must exhaust to outdoor air: 50 CFM for intermittent operation OR 20 CFM for continuous operation. Single bathroom with toilet and tub requires minimum 50 CFM. Exhaust ducts must terminate outside; damper required to prevent backflow.
Whole-House Ventilation
0.03 × floor area + 7.5 × bedrooms + 1
Minimum continuous outdoor air ventilation rate calculated as: 0.03 CFM per square foot of conditioned floor area plus 7.5 CFM per bedroom plus 1 CFM. System may be part of HVAC or dedicated ERV/HRV. Outdoor air intake must be located minimum 10 feet from exhaust or potential contaminant sources.
Duct Sealing
≤ 4 CFM25/100 sq ft for new, ≤ 8 for existing
New construction ductwork leakage limited to 4 CFM at 25 Pa per 100 square feet of duct surface area. Existing/retrofitted ductwork limited to 8 CFM. Tested via blower door method. Ductwork in conditioned space exempt from leakage testing.
Emergency Escape
Min 5.7 sq ft, 24" min height, 20" min width, max 44" sill
Bedrooms below grade or above grade without direct access to egress must have emergency escape window. Minimum opening: 5.7 sq ft (width × height ≥ 20" × 24"). Sill height maximum 44" above floor. Opening must be clear and operable from inside without tools.
Stairway Requirements
Max 7.75" riser, min 10" tread, min 36" width
Interior stairs: maximum riser height 7.75 inches, minimum tread depth 10 inches. Stair width minimum 36 inches clear. Risers must be uniform (variation ≤ 3/8 inch). Stair handrails required for stairs with 4+ risers; handrails 34-38 inches from nosing.
Guards Required
At 30"+ above grade, min 36" high
Guards (railings) required where floor/platform/stair is 30 inches or more above lower surface. Guard height minimum 36 inches from floor to top of rail (42 inches for stairs in certain jurisdictions). Balusters spaced maximum 4 inches on center. Horizontal rails spaced maximum 6 inches.
Automatic Fire Sprinklers
Required in new 1- and 2-family per MA adoption
Massachusetts fire code adoption requires automatic sprinkler system in all new construction 1- and 2-family dwellings. NFPA 13D wet-pipe system most common. System must be inspected and tested; backflow preventer required. Sprinkler heads in bedrooms must be heat-activated.
Carbon Monoxide Alarms
Required on every level + near bedrooms
Carbon monoxide alarms required on every level of dwelling, including basement. Alarms must also be installed in rooms with sleeping accommodations. Alarms must meet UL 2034 standard. Battery-powered or hardwired models acceptable; hardwired preferred.
Commercial Envelope
Prescriptive R-values by assembly type
780 CMR (Massachusetts energy code) specifies prescriptive U-values and R-values for commercial building envelopes by component type (walls, roofs, foundations). Different requirements based on building size and classification. Meets or exceeds IECC commercial requirements.
Enhanced Requirements for Stretch/Specialized Communities
15% more stringent than base 780 CMR
Municipalities may opt into MA Stretch Code (15% beyond standard 780 CMR). Requirements include higher insulation R-values, lower U-factors, reduced air leakage (2 ACH50), and electric-ready construction. Increasingly adopted by affluent MA towns.
Performance Path
Simulated performance ≥ standard reference design
Alternative compliance path using energy modeling. Home must demonstrate predicted annual source energy use ≤ standard reference design (prescriptive code path). Models use REM/Rate, EnergyGauge, or approved software. Detailed energy audit and modeling required; useful for innovative designs.
Energy Rating Index
ERI ≤ 55 for Zone 5A
Energy Rating Index (ERI) alternative compliance: home must achieve ERI ≤ 55 (compared to reference home score of 100). Uses ANSI/IECC rating methodology. Beneficial for high-efficiency homes that exceed prescriptive code. Requires third-party rating.
Blower Door Testing
CFM50, ACH50, NACH calculations
Blower door measures air leakage at 50 Pascal pressure (CFM50). Normalized to ACH50 (air changes per hour). NACH (natural air change rate) estimated using ACH50 / 20. Standard equipment: Minneapolis-based or equivalent door fan, gauge, and pressure transducer. Test must be conducted per ASTM E779.
Combustion Safety
CAZ depressurization test, CO limits
Combustion Appliance Zone (CAZ) depressurization test: open windows/doors, run exhaust fans (bath, range hood, dryer) and measure pressure. Pressure drop > 2 Pa indicates risk of combustion appliance backdraft. CO readings from natural gas appliances must be < 25 ppm at flue; spillage at draft hood indicates safety issue.
Air Sealing Work Scope
Priority list: attic bypasses, rim joist, etc.
Systematic air sealing prioritizes highest-impact leaks: attic bypasses (ceiling penetrations, rim joist tops), basement band joists, window sills and headers, electrical outlets in rim, plumbing penetrations, HVAC ductwork penetrations. Use blower door with smoke pencil to locate leaks; seal with caulk or expanding foam.
Insulation Standards
Grade I/II/III installation quality
Insulation quality graded: Grade I (best) = no visible gaps, proper orientation; Grade II (good) = minor gaps acceptable; Grade III (poor) = gaps, voids, compression, or improper coverage. Cavity insulation must fill 95%+ of space. Pipe/wire runs do not void entire bay. Proper attic ventilation spacing (e.g., soffit vents unblocked) required.