CODE BROWSER

Massachusetts residential building code reference

Filter by Category

23 of 23 sections

IRC R402.1.2

Insulation R-Values by Climate Zone

Zone 5A: Ceiling R-49, Wall R-20 or R-13+5ci, Floor R-30

Minimum insulation requirements for climate zone 5A (Boston, MA area). Ceiling assembly minimum R-49 value. Wall assemblies must achieve R-20 (cavity + continuous) or R-13 cavity with R-5 continuous insulation. Floor assemblies over unconditioned space require R-30 minimum.

IRCMA Amendment
IRC R402.4.1

Air Barrier & Insulation Installation

Requires continuous air barrier, tested ≤ 3 ACH50 for new construction

New construction must maintain continuous air barrier at thermal envelope. Blower door testing required to verify air tightness of ≤ 3 ACH50 (air changes per hour at 50 Pa). All penetrations, rim joists, and transitions must be sealed.

IRCMA Amendment
IRC R402.3.1

Fenestration U-Factor

Zone 5A: U-0.30 max

Window and sliding glass door assemblies in Zone 5A must not exceed U-factor of 0.30 (whole window, including frame). Fixed skylights U-0.38 max. Frameless glass skylights follow different requirements.

IRCMA Amendment
IRC R303.2.1

Vapor Retarders

Class I or II required on warm side in Zone 5A

Climate Zone 5A requires vapor retarder (≤ 1 perm) on the warm side of wall assemblies. Class I (≤ 0.1 perm) includes polyethylene sheet, foil-faced insulation. Class II (0.1–1 perm) includes kraft paper facings. Proper placement critical for moisture management.

IRCMA Amendment
IRC R402.2.4

Basement Wall Insulation

R-15ci or R-19 cavity

Basement walls below-grade must be insulated to R-15 continuous insulation OR R-19 cavity insulation. Continuous insulation (ci) preferred for thermal bridging reduction. Insulation may be placed on interior or exterior of wall; interior placement must be protected with fire-rated covering.

IRC
IRC M1601

Duct Sizing & Installation

Return air must equal supply, max 0.05" static per 100ft

Supply and return ductwork must be sized so total return air flow equals total supply air flow. Ductwork friction loss limited to 0.05 inches of water column per 100 feet of duct. Ducts must be sealed with mastic or tape rated for applications.

IRC
IRC M1502

Dryer Exhaust

Max 35ft equivalent, 4" smooth metal duct

Clothes dryer exhaust must use 4-inch smooth metal ductwork (rigid or flexible). Maximum equivalent length 35 feet (includes fittings and elbows; each elbow counts as 5 feet equivalent). Duct must terminate outside with damper. Flexible duct not to exceed 8 feet or 2 elbows.

IRC
IRC M1505

Bath Fan Requirements

50 CFM intermittent or 20 CFM continuous

Bathroom ventilation must exhaust to outdoor air: 50 CFM for intermittent operation OR 20 CFM for continuous operation. Single bathroom with toilet and tub requires minimum 50 CFM. Exhaust ducts must terminate outside; damper required to prevent backflow.

IRC
ASHRAE 62.2

Whole-House Ventilation

0.03 × floor area + 7.5 × bedrooms + 1

Minimum continuous outdoor air ventilation rate calculated as: 0.03 CFM per square foot of conditioned floor area plus 7.5 CFM per bedroom plus 1 CFM. System may be part of HVAC or dedicated ERV/HRV. Outdoor air intake must be located minimum 10 feet from exhaust or potential contaminant sources.

ASHRAEMA Amendment
IRC N1103.3

Duct Sealing

≤ 4 CFM25/100 sq ft for new, ≤ 8 for existing

New construction ductwork leakage limited to 4 CFM at 25 Pa per 100 square feet of duct surface area. Existing/retrofitted ductwork limited to 8 CFM. Tested via blower door method. Ductwork in conditioned space exempt from leakage testing.

IRCMA Amendment
IRC R310.1

Emergency Escape

Min 5.7 sq ft, 24" min height, 20" min width, max 44" sill

Bedrooms below grade or above grade without direct access to egress must have emergency escape window. Minimum opening: 5.7 sq ft (width × height ≥ 20" × 24"). Sill height maximum 44" above floor. Opening must be clear and operable from inside without tools.

IRC
IRC R311.7

Stairway Requirements

Max 7.75" riser, min 10" tread, min 36" width

Interior stairs: maximum riser height 7.75 inches, minimum tread depth 10 inches. Stair width minimum 36 inches clear. Risers must be uniform (variation ≤ 3/8 inch). Stair handrails required for stairs with 4+ risers; handrails 34-38 inches from nosing.

IRC
IRC R312.1

Guards Required

At 30"+ above grade, min 36" high

Guards (railings) required where floor/platform/stair is 30 inches or more above lower surface. Guard height minimum 36 inches from floor to top of rail (42 inches for stairs in certain jurisdictions). Balusters spaced maximum 4 inches on center. Horizontal rails spaced maximum 6 inches.

IRC
IRC R313

Automatic Fire Sprinklers

Required in new 1- and 2-family per MA adoption

Massachusetts fire code adoption requires automatic sprinkler system in all new construction 1- and 2-family dwellings. NFPA 13D wet-pipe system most common. System must be inspected and tested; backflow preventer required. Sprinkler heads in bedrooms must be heat-activated.

IRCMA Amendment
IRC R315

Carbon Monoxide Alarms

Required on every level + near bedrooms

Carbon monoxide alarms required on every level of dwelling, including basement. Alarms must also be installed in rooms with sleeping accommodations. Alarms must meet UL 2034 standard. Battery-powered or hardwired models acceptable; hardwired preferred.

IRCMA Amendment
780 CMR C402.1

Commercial Envelope

Prescriptive R-values by assembly type

780 CMR (Massachusetts energy code) specifies prescriptive U-values and R-values for commercial building envelopes by component type (walls, roofs, foundations). Different requirements based on building size and classification. Meets or exceeds IECC commercial requirements.

780 CMRMA Amendment
780 CMR Stretch Code

Enhanced Requirements for Stretch/Specialized Communities

15% more stringent than base 780 CMR

Municipalities may opt into MA Stretch Code (15% beyond standard 780 CMR). Requirements include higher insulation R-values, lower U-factors, reduced air leakage (2 ACH50), and electric-ready construction. Increasingly adopted by affluent MA towns.

780 CMRMA Amendment
IECC R405

Performance Path

Simulated performance ≥ standard reference design

Alternative compliance path using energy modeling. Home must demonstrate predicted annual source energy use ≤ standard reference design (prescriptive code path). Models use REM/Rate, EnergyGauge, or approved software. Detailed energy audit and modeling required; useful for innovative designs.

IECC
IECC R406

Energy Rating Index

ERI ≤ 55 for Zone 5A

Energy Rating Index (ERI) alternative compliance: home must achieve ERI ≤ 55 (compared to reference home score of 100). Uses ANSI/IECC rating methodology. Beneficial for high-efficiency homes that exceed prescriptive code. Requires third-party rating.

IECCMA Amendment
BPI BA Ch 22

Blower Door Testing

CFM50, ACH50, NACH calculations

Blower door measures air leakage at 50 Pascal pressure (CFM50). Normalized to ACH50 (air changes per hour). NACH (natural air change rate) estimated using ACH50 / 20. Standard equipment: Minneapolis-based or equivalent door fan, gauge, and pressure transducer. Test must be conducted per ASTM E779.

BPI
BPI BA Ch 15

Combustion Safety

CAZ depressurization test, CO limits

Combustion Appliance Zone (CAZ) depressurization test: open windows/doors, run exhaust fans (bath, range hood, dryer) and measure pressure. Pressure drop > 2 Pa indicates risk of combustion appliance backdraft. CO readings from natural gas appliances must be < 25 ppm at flue; spillage at draft hood indicates safety issue.

BPI
BPI BA Ch 17

Air Sealing Work Scope

Priority list: attic bypasses, rim joist, etc.

Systematic air sealing prioritizes highest-impact leaks: attic bypasses (ceiling penetrations, rim joist tops), basement band joists, window sills and headers, electrical outlets in rim, plumbing penetrations, HVAC ductwork penetrations. Use blower door with smoke pencil to locate leaks; seal with caulk or expanding foam.

BPI
BPI BA Ch 19

Insulation Standards

Grade I/II/III installation quality

Insulation quality graded: Grade I (best) = no visible gaps, proper orientation; Grade II (good) = minor gaps acceptable; Grade III (poor) = gaps, voids, compression, or improper coverage. Cavity insulation must fill 95%+ of space. Pipe/wire runs do not void entire bay. Proper attic ventilation spacing (e.g., soffit vents unblocked) required.

BPI